EXELTECH-MIB DEFINITIONS ::= BEGIN IMPORTS TRAP-TYPE FROM RFC-1215 OBJECT-TYPE FROM RFC-1212 DisplayString FROM SNMPv2-TC enterprises, IpAddress FROM RFC1155-SMI; -- validated with https://www.muonics.com/Tools/smicheck.php -- Author Raymond Sgroi 7/29/2024 exeltechKCMIB OBJECT IDENTIFIER ::= { enterprises 30320 } -- these are the objects kcSysMon OBJECT IDENTIFIER ::= { exeltechKCMIB 2 } objects OBJECT IDENTIFIER ::= { kcSysMon 0 } battery OBJECT IDENTIFIER ::= { objects 1 } phase1 OBJECT IDENTIFIER ::= { objects 2 } phase2 OBJECT IDENTIFIER ::= { objects 3 } phase3 OBJECT IDENTIFIER ::= { objects 4 } alarms OBJECT IDENTIFIER ::= { objects 5 } settings OBJECT IDENTIFIER ::= { objects 6 } system OBJECT IDENTIFIER ::= { objects 7 } -- object defines -- -- battery objects -- batDCV OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The battery voltage. Displayed in deciVolts. Divide by 10 to get DC voltage." ::= { battery 1 } batDCI OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The battery current. Displayed in amps." ::= { battery 2 } batABUS OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The A bus DC voltage if present. Displayed in DC Volts." ::= { battery 3 } batBBUS OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The B bus DC voltage if present. Displayed in DC Volts." ::= { battery 4 } -- -- phase 1 objects -- utilityAcvL1 OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The Inverter AC voltage of phase 1. Displayed in AC Volts." ::= { phase1 1 } utilityAciL1 OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The Inverter current of phase 1. Displayed in amps." ::= { phase1 2 } utilityFrqL1 OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The Inverter frequency of phase 1. Displayed in hertz." ::= { phase1 3 } inverterAcvL1 OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The Utility AC voltage of phase 1. Displayed in AC Volts." ::= { phase1 4 } inverterAciL1 OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The Utility current of phase 1. Displayed in amps." ::= { phase1 5 } inverterFrqL1 OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The Utility frequency of phase 1. Displayed in hertz." ::= { phase1 6 } line1AcvOut OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The Output Voltage of phase 1. Displayed in AC volts" ::= { phase1 7 } temperatureSTSL1 OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The the SCR temperature of phase 1. Displayed in Degrees C." ::= { phase1 8 } -- -- phase 2 objects -- utilityAcvL2 OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The Inverter AC voltage of phase 2. Displayed in AC Volts." ::= { phase2 1 } utilityAciL2 OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The Inverter current of phase 2. Displayed in amps." ::= { phase2 2 } utilityFrqL2 OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The Inverter frequency of phase 2. Displayed in hertz." ::= { phase2 3 } inverterAcvL2 OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The Utility AC voltage of phase 2. Displayed in AC Volts." ::= { phase2 4 } inverterAciL2 OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The Utility current of phase 2. Displayed in amps." ::= { phase2 5 } inverterFrqL2 OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The Utility frequency of phase 2. Displayed in hertz." ::= { phase2 6 } line2ACVOut OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The Output Voltage of phase 2. Displayed in AC volts" ::= { phase2 7 } temperatureSTSL2 OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The the SCR temperature of phase 2. Displayed in Degrees C." ::= { phase2 8 } -- -- phase 3 objects -- utilityAcvL3 OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The Inverter AC voltage of phase 3. Displayed in AC Volts." ::= { phase3 1 } utilityAciL3 OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The Inverter current of phase 3. Displayed in amps." ::= { phase3 2 } utilityFrqL3 OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The Inverter frequency of phase 3. Displayed in hertz." ::= { phase3 3 } inverterAcvL3 OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The Utility AC voltage of phase 3. Displayed in AC Volts." ::= { phase3 4 } inverterAciL3 OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The Utility current of phase 3. Displayed in amps." ::= { phase3 5 } inverterFrqL3 OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The Utility frequency of phase 3. Displayed in hertz." ::= { phase3 6 } line3ACVOut OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The Output Voltage of phase 3. Displayed in AC volts" ::= { phase3 7 } temperatureSTSL3 OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "The the SCR temperature of phase 3. Displayed in Degrees C." ::= { phase3 8 } -- -- alarms objects -- systemAlarms OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Alarms Status: This is a 4 byte and each bit represents an alarm. 0x00000001 - Low DC Volt Alarm 0x00000002 - Power Module Fail 0x00000004 - NA 0x00000008 - PowerLvlIndicator 0x00000010 - Module Temperature Warning 0x00000020 - Module Local Disable 0x00000040 - cage comm failure detected 0x00000080 - AB Bus Fail Detect 0x00000100 - System Disable 0x00000200 - Power Module fail detected 0x00000400 - Slot Not Detected fault 0x00000800 - Ph1 on Ref2 0x00001000 - Ph1 on Ref2 0x00002000 - Ph1 on Ref2 0x00004000 - NA 0x00008000 - NA 0x00010000 - Utility Primary 0x00020000 - Inverter source fault 0x00040000 - Utility source fault 0x00080000 - MBS Lockout Asserted 0x00100000 - Sources not sync 0x00200000 - Fan fault detect STS PowerSwitch 0x00400000 - Warm Temp STS PowerSwitch 0x00800000 - Overtemp STS PowerSwitch 0x01000000 - SCR Active (Legacy) 0x02000000 - Utility SCR Driving 0x04000000 - STS Backfeed protection enabled 0x08000000 - Line 2 Line fail 0x10000000 - STS Forced Inverter State 0x20000000 - STS Forced Utility State 0x40000000 - STS Forced Contactor Open 0x80000000 - STS Contactor Open Detected" ::= { alarms 1 } slotAlarms OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Alarms Status: This is a 4 byte and each bit represents a slot not communicating. 0x00000001 - Slot 1 not detected 0x00000002 - Slot 2 not detected 0x00000004 - Slot 3 not detected 0x00000008 - Slot 4 not detected 0x00000010 - Slot 5 not detected 0x00000020 - Slot 6 not detected 0x00000040 - Slot 7 not detected 0x00000080 - Slot 8 not detected 0x00000100 - Slot 9 not detected 0x00000200 - Slot 10 not detected 0x00000400 - Slot 11 not detected 0x00000800 - n/a 0x00001000 - n/a 0x00002000 - n/a 0x00004000 - n/a 0x00008000 - n/a" ::= { alarms 2 } alarmOne OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Alarms Status: 0 is no Alarm, 1 is any configured Alarm 1 bit set with the corrisponding alarm 1 bit set." ::= { alarms 3 } alarmTwo OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Alarms Status: 0 is no Alarm, 1 is any configured Alarm 2 bit set with the corrisponding alarm 2 bit set." ::= { alarms 4 } -- -- settings objects -- dCVLow OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "This value is the low DC Voltage limit for sending traps. The voltage needs to be set in deciVolts. Multiply the voltage by 10 and then send that value." ::= { settings 1 } dCVHigh OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "This value is the high DC Voltage limit for sending traps. The voltage needs to be set in deciVolts. Multiply the voltage by 10 and then send that value." ::= { settings 2 } alarm1Configuration OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The Current internal bitstate configurations for Alarm 1 Use ProductStatus to modify Configurations" ::= { settings 3 } alarm2Configuration OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The Current internal bitstate configurations for Alarm 2 Use ProductStatus to modify Configurations" ::= { settings 4 } slotConfiguration OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The Current internal bitstate configurations for module slot alarms" ::= { settings 5 } trap-target-ip1 OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "Ip address of the first manager for traps. Set to zero to STOP TRAPS from sending" ::= { settings 6 } trap-target-ip2 OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "Ip address of the second manager for traps. Set to zero to remove target" ::= { settings 7 } trap-target-ip3 OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "Ip address of the third manager for traps. Set to zero to remove target" ::= { settings 8 } ipAddressStatic OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "The System static IP Address" ::= { settings 9 } subnetMaskStatic OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "The System IP subnet mask" ::= { settings 10 } defaultGatewayStatic OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "The System IP Gateway Address" ::= { settings 11 } setNetworkConfig OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Integer value indicationg Static IP usage or DHCP usage, also any additional networking properties" ::= { settings 12 } ---------------------------------------------------------------------------------------------------------- ntp-ip1 OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "Ip address of the SNTP server" ::= { settings 13 } ntp-set OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Timezone settings For SNTP configuration" ::= { settings 14 } traps-config OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "configuration setting for the All-good traps, 0-255 where the period between All-good traps is 30 seconds*VALUE, zero is off" ::= { settings 15 } logging-config OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "configuration setting logging, factory use only" ::= { settings 16 } ---------------------------------------------------------------------------------------------------- -- -- V1/V2 trap syntax -- lowDCtrap TRAP-TYPE ENTERPRISE batDCV VARIABLES { batDCV, dCVLow } DESCRIPTION "Battery voltage low limit has been triggered." ::= 1 highDCtrap TRAP-TYPE ENTERPRISE batDCV VARIABLES { batDCV, dCVHigh } DESCRIPTION "Battery voltage high limit has been triggered." ::= 2 alarmConfig1trap TRAP-TYPE ENTERPRISE alarms VARIABLES { alarm1Configuration, systemAlarms} DESCRIPTION "A minor alarm has been triggered." ::= 3 alarmConfig2trap TRAP-TYPE ENTERPRISE alarms VARIABLES { alarm2Configuration, systemAlarms} DESCRIPTION "A major alarm has been triggered." ::= 4 generalAlarmtrap TRAP-TYPE ENTERPRISE alarms VARIABLES { alarmOne, alarmTwo } DESCRIPTION "A general Status update" ::= 5 slotAlarmtrap TRAP-TYPE ENTERPRISE alarms VARIABLES { slotAlarms } DESCRIPTION "A general Status update" ::= 6 --alarmOne ------------------------------------------------------------------------------------------------ -- system objects -- systemName OBJECT-TYPE SYNTAX DisplayString (SIZE (0..255)) ACCESS read-write STATUS mandatory DESCRIPTION "System barcode pn" ::= { system 1 } systemSerial OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "System serial number" ::= { system 2 } -------------------------------------------------------end of SNMP entered System Part number monitorName OBJECT-TYPE SYNTAX DisplayString (SIZE (0..255)) ACCESS read-only STATUS mandatory DESCRIPTION "Monitor card barcode pn" ::= { system 3 } monitorSer OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Monitor card serial number" ::= { system 4 } -------------------------------------------------------end of Monitor/Controller card slot1Name OBJECT-TYPE SYNTAX DisplayString (SIZE (0..255)) ACCESS read-only STATUS mandatory DESCRIPTION "module Barcode pn" ::= { system 5 } slot1Ser OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module serial number" ::= { system 6 } slot1Fan OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module fanspeed" ::= { system 7 } slot1Temp OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module Temperature" ::= { system 8 } slot1St OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module Status bits" ::= { system 9 } slot1Out OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module output level" ::= { system 10 } -------------------------------------------------------end of individual module 1 slot2Name OBJECT-TYPE SYNTAX DisplayString (SIZE (0..255)) ACCESS read-only STATUS mandatory DESCRIPTION "module Barcode pn" ::= { system 11 } slot2Ser OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module serial number" ::= { system 12 } slot2Fan OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module fanspeed" ::= { system 13 } slot2Temp OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module Temperature" ::= { system 14 } slot2St OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module Status bits" ::= { system 15 } slot2Out OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module output level" ::= { system 16 } -------------------------------------------------------end of individual module 2 slot3Name OBJECT-TYPE SYNTAX DisplayString (SIZE (0..255)) ACCESS read-only STATUS mandatory DESCRIPTION "module Barcode pn" ::= { system 17 } slot3Ser OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module serial number" ::= { system 18 } slot3Fan OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module fanspeed" ::= { system 19 } slot3Temp OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module Temperature" ::= { system 20 } slot3St OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module Status bits" ::= { system 21 } slot3Out OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module output level" ::= { system 22 } -------------------------------------------------------end of individual module 3 slot4Name OBJECT-TYPE SYNTAX DisplayString (SIZE (0..255)) ACCESS read-only STATUS mandatory DESCRIPTION "module Barcode pn" ::= { system 23 } slot4Ser OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module serial number" ::= { system 24 } slot4Fan OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module fanspeed" ::= { system 25 } slot4Temp OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module Temperature" ::= { system 26 } slot4St OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module Status bits" ::= { system 27 } slot4Out OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module output level" ::= { system 28 } -------------------------------------------------------end of individual module 4 slot5Name OBJECT-TYPE SYNTAX DisplayString (SIZE (0..255)) ACCESS read-only STATUS mandatory DESCRIPTION "module Barcode pn" ::= { system 29 } slot5Ser OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module serial number" ::= { system 30 } slot5Fan OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module fanspeed" ::= { system 31 } slot5Temp OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module Temperature" ::= { system 32 } slot5St OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module Status bits" ::= { system 33 } slot5Out OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module output level" ::= { system 34 } -------------------------------------------------------end of individual module 5 slot6Name OBJECT-TYPE SYNTAX DisplayString (SIZE (0..255)) ACCESS read-only STATUS mandatory DESCRIPTION "module Barcode pn" ::= { system 35 } slot6Ser OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module serial number" ::= { system 36 } slot6Fan OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module fanspeed" ::= { system 37 } slot6Temp OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module Temperature" ::= { system 38 } slot6St OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module Status bits" ::= { system 39 } slot6Out OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module output level" ::= { system 40 } -------------------------------------------------------end of individual module 6 slot7Name OBJECT-TYPE SYNTAX DisplayString (SIZE (0..255)) ACCESS read-only STATUS mandatory DESCRIPTION "module Barcode pn" ::= { system 41 } slot7Ser OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module serial number" ::= { system 42 } slot7Fan OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module fanspeed" ::= { system 43 } slot7Temp OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module Temperature" ::= { system 44 } slot7St OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module Status bits" ::= { system 45 } slot7Out OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module output level" ::= { system 46 } -------------------------------------------------------end of individual module 7 slot8Name OBJECT-TYPE SYNTAX DisplayString (SIZE (0..255)) ACCESS read-only STATUS mandatory DESCRIPTION "module Barcode pn" ::= { system 47 } slot8Ser OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module serial number" ::= { system 48 } slot8Fan OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module fanspeed" ::= { system 49 } slot8Temp OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module Temperature" ::= { system 50 } slot8St OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module Status bits" ::= { system 51 } slot8Out OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module output level" ::= { system 52 } -------------------------------------------------------end of individual module 8 slot9Name OBJECT-TYPE SYNTAX DisplayString (SIZE (0..255)) ACCESS read-only STATUS mandatory DESCRIPTION "module Barcode pn" ::= { system 53 } slot9Ser OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module serial number" ::= { system 54 } slot9Fan OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module fanspeed" ::= { system 55 } slot9Temp OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module Temperature" ::= { system 56 } slot9St OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module Status bits" ::= { system 57 } slot9Out OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module output level" ::= { system 58 } -------------------------------------------------------end of individual module 9 slot10Name OBJECT-TYPE SYNTAX DisplayString (SIZE (0..255)) ACCESS read-only STATUS mandatory DESCRIPTION "module Barcode pn" ::= { system 59 } slot10Ser OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module serial number" ::= { system 60 } slot10Fan OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module fanspeed" ::= { system 61 } slot10Temp OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module Temperature" ::= { system 62 } slot10St OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module Status bits" ::= { system 63 } slot10Out OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module output level" ::= { system 64 } -------------------------------------------------------end of individual module 10 slot11Name OBJECT-TYPE SYNTAX DisplayString (SIZE (0..255)) ACCESS read-only STATUS mandatory DESCRIPTION "module Barcode pn" ::= { system 65 } slot11Ser OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module serial number" ::= { system 66 } slot11Fan OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module fanspeed" ::= { system 67 } slot11Temp OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module Temperature" ::= { system 68 } slot11St OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module Status bits" ::= { system 69 } slot11Out OBJECT-TYPE SYNTAX INTEGER (0..16777215) ACCESS read-only STATUS mandatory DESCRIPTION "module output level" ::= { system 70 } -------------------------------------------------------end of individual module 11 END